| RDW8 | HU | 25 | 16 | 3 | H | Tingkat laci | AC230V | Teu aya tegangan handap |
| Kode produk | Ngalanggar nilai | Arus pigura | Arus anu dipeunteun | Jumlah kutub | Pangontrol | Modeu pamasangan | Tegangan kontrol | Lampiran |
| Tegangan tinggi anu cerdas Pemutus sirkuit universal | HU | 25:2500(06-25) 40:4000(08-40) 63:6300(40-63) | 06:630A 08:800A 10:1000A 12:1250A 16:1600A 20:2000A 25:2500A 29:2900A 32:3200A 36:3600A 40:4000A 50:5000A 60:6000A | 3:3P 4:4P | M: Tipe standar (Tampilan digital) R: Tipe anu ditingkatkeun (Layar kristal cair) H: Tipe canggih (LCD kalayan komunikasi) | Tingkat laci Laci vertikal Tingkat tetep Vertikal tetep | AC230V AC400V DC220V DC110V | Partisi antarfase Transformasi opat kali lipat Rangka panto Teu aya tegangan handap Undervoltage instan Dina waktos kalénder Interlocking mékanis Interlocking mékanis Hiji konci, hiji konci Dua konci sareng hiji konci Tilu konci, dua konci Éta 50-50 Genep asup, genep off |
● Konfigurasi standar standar RDW8HU: shunt, panutupan, operasi listrik, konvérsi 4 grup, pigura panto, partisi interfase
● Contona: peryogi mesen RDW8HU-2500, laci tilu kutub, arus nu dipeunteun 1250A, pangontrol cerdas pikeun tipe R, tegangan kontrol AC230V
● Diébréhkeun salaku: RDW8HU-25 12/3R tingkat laci AC230V tanpa tegangan handap.
Kaayaan kerja normal
■ Suhu hawa di sabudeureun nyaéta -5℃ ~ +40℃, sareng nilai rata-rata 24 jam henteu ngaleuwihan +35°C;
Catetan:Upami wates luhur ngaleuwihan +40℃ atanapi wates handap langkung handap tibatan -5℃, pangguna kedah negosiasi sareng produsén.
■ Élévasi lokasi pamasangan teu ngaleuwihan 2000m;
Catetan:Konsultasikeun ka produsén pikeun pemutus sirkuit anu dianggo di lingkungan kerja anu jangkungna langkung ti 2000 m.
■ Kalembaban relatif atmosfir henteu ngaleuwihan 50% nalika suhu hawa sakitar +40℃; Éta tiasa ngagaduhan kalembaban relatif anu langkung luhur dina suhu anu langkung handap. Salaku conto, bulan anu paling baseuh ngagaduhan kalembaban relatif maksimum rata-rata 90%, sedengkeun suhu minimum rata-rata dina bulan éta nyaéta +20℃, sareng tindakan pangobatan kedah dilaksanakeun pikeun kondensasi anu kadang-kadang kusabab parobahan suhu.
■ Tingkat polusi nyaéta 3;
■ Nalika tegangan kerja anu dipeunteun tina sirkuit utama nyaéta AC 800V ~ AC1140V, sirkuit kontrol sareng sirkuit bantu kedah diisolasi tina sirkuit utama ku transformator, sareng tegangan kerja maksimum tina sirkuit kontrol sareng sirkuit bantu nyaéta AC400V, kategori pamasangan sirkuit kontrol sareng sirkuit bantu nyaéta Ⅲ;
■Pemutus sirkuit ieu cocog pikeun lingkungan éléktromagnétik A;
■Anggo kategori B.
Kaayaan pamasangan normal
■ Pamasangan pemutus sirkuit tetep: Pemutus sirkuit disimpen dina kabinet distribusi sareng diamankeun ku baut sareng ring M10 (pigura cangkang langkung ti 2500A).
Pemutus sirkuit dipasang kalayan lancar tanpa tekanan mékanis tambahan.Hindarkeun karusakan pemutus sirkuit atanapi kontak busbar utama anu goréng;
■ Pamasangan pemutus sirkuit tipe laci: Cabut awak pemutus sirkuit tina korsi laci, pasang korsi laci dina distribusikabinet heula,sareng kencengkeun nganggo baut sareng ring M10 (langkung ti 2500A). Tingkat pemasangan pemutus sirkuit stabil, teu kedah aya setrés mékanis tambahan, supados nyingkahan karusakan pemutus sirkuit atanapi kontak anu goréng antara beus utama sarengsirkuit sekundér,saatos réngsé awak pemutus sirkuit kana posisi sambungan korsi laci;
■Pemutus sirkuit kedah dipasang di tempat anu tanpa résiko ledakan sareng lebu konduktif, tanpa cekap pikeun ngakorosi logam sarengngancurkeun insulasi;
■Tingkat panyalindunganna nyaéta IP20, Nalika pemutus sirkuit dipasang dina kabinet sareng pigura panto dipasang, tingkat panyalindungan tiasangahontal IP40.
Kaayaan panyimpenan sareng transportasi normal
■ Wates suhu handap teu kurang ti -25℃, wates luhur teu leuwih ti +55℃; Kalembaban relatif (+25℃) teu ngaleuwihan95%;
■Produk ieu kedah diurus kalayan ati-ati nalika diangkut, sareng henteu kedah dibalikkeun pikeun nyingkahan tabrakan anu telenges.
| Jumlah kutub (Tabel 1) | 3P/4P | ||||||||
| Frékuénsi | 50/60Hz | ||||||||
| Tegangan operasi anu dipeunteun Ue(V) | AC800V/AC1000V/AC1140V | ||||||||
| Tegangan tahan impuls anu dipeunteun Uimp (kV) | AC12kV | ||||||||
| Tegangan insulasi anu dipeunteun Ui(V) | AC1250V | ||||||||
| Kelas pigura | 25HU | 40HU | 63HU | ||||||
| Dina (A) | |||||||||
| 630 | ● | ||||||||
| 800 | ● | ● | |||||||
| 1000 | ● | ● | |||||||
| 1250 | ● | ● | |||||||
| 1600 | ● | ● | |||||||
| 2000 | ● | ● | |||||||
| 2500 | ● | ● | |||||||
| 2900 | ● | ||||||||
| 3200 | ● | ||||||||
| 3600 | ● | ||||||||
| 4000 | ● | ● | |||||||
| 5000 | ● | ||||||||
| 6300 | ● | ||||||||
| Kapasitas pegat (AC800V) | AC800V | AC1000V | AC1140V | AC800V | AC1000V | AC1140V | AC800V | AC1000V | AC1140V |
| Kapasitas pegat sirkuit pondok wates anu dipeunteun Icu(KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Kapasitas pegat sirkuit pondok operasi anu dipeunteun Ics (KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Daya tahan jangka pondok anu dipeunteun Icw/1s(KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Waktos segmen pinuh (teu aya reureuh tambahan) | 25 ~ 30ms | ||||||||
| Waktos panutupan | ≤70ms | ||||||||
| Umur mékanis (kalayan pangropéa) | 20000 | 20000 | 13000 | ||||||
| Umur mékanis (teu aya pangropéa) | 10000 | 10000 | 6500 | ||||||
| Kahirupan listrik | 7000 | 6000 | 1500 | ||||||
| Modeu sambungan (horizontal) | ● | ||||||||
| Modeu sambungan (vertikal) | ● | ||||||||
| Modeu sambungan (horizontal luhur sareng vertikal handap) Modeu sambungan (vertikal ka luhur sareng horizontal ka handap) | ● | ||||||||
Catetan:Umur mékanis korsi laci nyaéta 100 kali, ti "pamisahan" dugi ka "sambungan" dugi ka "pamisahan" ngan sakali, sareng siklus operasi nyaéta 1 kali / 2 menit.
①Modél pangontrol anu calakan(modél produk anu saluyu);
②Jandéla tampilan kristal cair LCD: tiasa nampilkeun unggal nilai arus fase, nilai tegangan, parameter setélan, arus gangguan, aliran, waktos perjalanan sareng parameter pamundut inpormasi;
③Indikasi gangguan reureuh lila anu kaleuleuwihi;
④Indikasi gangguan waktu tibalik reureuh pondok sirkuit pondok;
⑤Indikasi gangguan taneuh atanapi nétral;
⑥Konci setélan:Gancang pindah ka menu utama setélan parameter, (dina antarmuka input kecap akses aya konci "Katuhu");
⑦Konci pangukuran:Gancang pindah ka menu utama standar pangukuran, (di handapeun antarmuka input kecap akses aya tombol "Kénca");
⑧Konci Naék:Pindahkeun eusi menu ka luhur dina tingkat ayeuna, atanapi robih pilihan ka luhur Parameter;
⑨Konci Turun:Pindahkeun eusi menu ka handap dina tingkat ayeuna, atanapi robih pilihan ka handap Parameter;
⑩Konci tukang:Kaluar ti tingkat ayeuna pikeun asup ka menu tingkat luhur, atanapi ngabolaykeun parameter ayeuna anu dipilih;
⑪Konci Ok:Lebetkeun menu tingkat salajengna anu ditunjuk ku item ayeuna, atanapi teraskeun ka parameter ayeuna Pilih, simpen parobihan anu dilakukeun;
⑫Konci pamundut:Pindah ka menu téma riwayat sareng pangropéa;
⑬Konci setélan parameter panyalindungan:Pindah ka menu téma setélan parameter panyalindungan;
⑭Indikasi gangguan sakedapan sirkuit pondok;
Indikasi gangguan waktos tetep reureuh pondok sirkuit pondok;
⑯Indikasi komunikasi:
Profibus: teu aya komunikasi nalika pareum, komunikasi lampu konstan;
Modbus: pareum nalika teu aya komunikasi sareng kedip-kedip nalika komunikasi sayogi.
⑰Indikasi normal:dina kaayaan daya, kaayaan kerja normal, LED sok kedip-kedip héjo;
⑱Indikasi gangguan/alarmLED "kasalahan/alarm" teu hurung nalika operasi normal; rusak nalika trip, LED "Kasalahan/alarm" beureum sareng kedip-kedip gancang; Upami aya alarm nalika LED beureum tetep caang;
⑲Tombol ResetNalika pangontrol calakan aya dina kaayaan gangguan/alarm, éta kedah mulangkeun kana kaayaan kerja normal, pencét tombol ieu pikeun ngahapus indikasi gangguan/alarm pangontrol calakan.
| Nilai set arus aksi Ir (Tabel 2) | (0.4~1.0)Asup+PAreuman | Toleransi ayeuna | ±10% | ||||||||||||||
| Arus anu diterapkeun I | Nyetél waktos perjalanan | ||||||||||||||||
| 1.05Ir | >2 jam teu bisa gerak | ||||||||||||||||
| 1.3Ir | < 1 jam Perjalanan | ||||||||||||||||
| Jenis ciri panyalindungan | Arus gangguan | Setel waktos Tr (s) | |||||||||||||||
| Waktos tibalik standar SI | 1.5Ir | 0.61 | 0.98 | 1.47 | 2.46 | 3.68 | 4.91 | 6.14 | 9.21 | 11.05 | 17.19 | 24.56 | 36.84 | 49.13 | 61.41 | 73.69 | 85.97 |
| 2Ir | 0.36 | 0.57 | 0.86 | 1.43 | 2.15 | 2.87 | 3.58 | 5.37 | 6.45 | 10.03 | 14.33 | 21.49 | 28.65 | 35.82 | 42.98 | 50.15 | |
| 6Ir | 0.14 | 0.22 | 0.33 | 0.55 | 0.82 | 1.1 | 1.37 | 2.06 | 2.47 | 3.84 | 5.48 | 8.22 | 10.96 | 13.7 | 16.45 | 19.19 | |
| 7.2Ir | 0.12 | 0.2 | 0.3 | 0.5 | 0.74 | 0.99 | 1.24 | 1.86 | 2.23 | 3.48 | 4.97 | 7.45 | 9.93 | 12.42 | 14.9 | 17.38 | |
| Waktu tibalik laju VI | 1.5Ir | 2 | 3.2 | 4.8 | 8 | 12 | 16 | 20 | 27 | 36.6 | 56 | 80 | 120 | 160 | 200 | 240 | 280 |
| 2Ir | 1 | 1.6 | 2.4 | 4 | 6 | 8 | 10 | 13.5 | 18 | 28 | 40 | 60 | 80 | 100 | 120 | 140 | |
| 6Ir | 0.2 | 0.32 | 0.48 | 0.8 | 1.2 | 1.6 | 2 | 2.7 | 3.6 | 5.6 | 8 | 12 | 16 | 20 | 24 | 28 | |
| 7.2Ir | 0.16 | 0.26 | 0.39 | 0.65 | 0.97 | 1.29 | 1.61 | 2.18 | 2.9 | 4.52 | 6.45 | 9.68 | 12.9 | 16.13 | 19.35 | 22.58 | |
| Waktos tibalik EI(G)Express (Protéksi distribusi umum) | 1.5Ir | 8 | 12.8 | 19.2 | 32 | 48 | 64 | 80 | 108 | 144 | 224 | 320 | 480 | 640 | 800 | 960 | 1000 |
| 2Ir | 3.33 | 5.33 | 8 | 13.33 | 20 | 26.67 | 33.33 | 45 | 60 | 93.33 | 133.33 | 200 | 266.67 | 333.33 | 400 | 433.33 | |
| 6Ir | 0.29 | 0.46 | 0.69 | 1.14 | 1.71 | 2.29 | 2.86 | 3.86 | 5.14 | 8 | 11.43 | 17.14 | 22.86 | 28.57 | 34.29 | 37.14 | |
| 7.2Ir | 0.2 | 0.31 | 0.47 | 0.79 | 1.18 | 1.57 | 1.97 | 2.66 | 3.58 | 5.51 | 7.87 | 11.8 | 15.74 | 19.67 | 23.6 | 25.57 | |
| Waktos tibalik EI(M)Express (Protéksi motor) | 1.5Ir | 6.22 | 9.96 | 14.93 | 24.89 | 37.34 | 49.78 | 62.23 | 84.01 | 112.01 | 174.24 | 248.91 | 373.37 | 497.82 | 622.28 | 746.73 | 208.96 |
| 2Ir | 2.95 | 4.72 | 7.07 | 11.79 | 17.69 | 23.58 | 29.48 | 39.79 | 53.06 | 82.53 | 117.9 | 176.86 | 235.81 | 294.76 | 353.71 | 383.19 | |
| 6Ir | 0.28 | 0.45 | 0.68 | 1.13 | 1.69 | 2.26 | 2.82 | 3.81 | 5.08 | 7.9 | 11.29 | 16.94 | 22.58 | 28.23 | 33.88 | 36.7 | |
| 7.2Ir | 0.2 | 0.31 | 0.47 | 0.78 | 1.17 | 1.56 | 1.95 | 2.63 | 3.51 | 5.46 | 7.8 | 11.7 | 15.61 | 19.51 | 23.41 | 25.56 | |
| Sekering tegangan tinggi HV cocog | 1.5Ir | 2.46 | 3.94 | 5.91 | 9.85 | 14.77 | 19.69 | 24.62 | 33.23 | 44.31 | 68.92 | 98.46 | 147.69 | 196.92 | 246.15 | 295.38 | 320 |
| 2Ir | 0.67 | 1.07 | 1.6 | 2.67 | 4 | 5.33 | 6.67 | 9 | 12 | 18.67 | 26.67 | 40 | 53.33 | 66.67 | 80 | 86.67 | |
| 6Ir | 0.01 | 0.01 | 0.02 | 0.03 | 0.05 | 0.06 | 0.08 | 0.1 | 0.14 | 0.22 | 0.31 | 0.46 | 0.62 | 0.77 | 0.93 | 1 | |
| 7.2Ir | 0 | 0.01 | 0.01 | 0.01 | 0.02 | 0.03 | 0.04 | 0.05 | 0.07 | 0.1 | 0.15 | 0.22 | 0.3 | 0.37 | 0.45 | 0.48 | |
| I²T panyalindungan waktos tibalik universal | 1.5Ir | 15 | 30 | 60 | 120 | 240 | 360 | 480 | 600 | 720 | 840 | 960 | |||||
| 2Ir | 8.44 | 16.88 | 33.75 | 67.5 | 135 | 202.5 | 270 | 337.5 | 405 | 472.5 | 540 | ||||||
| 6Ir | 0.94 | 1.88 | 3.75 | 7.5 | 15 | 22.5 | 30 | 37.5 | 45 | 52.5 | 60 | ||||||
| 7.2Ir | 0.65 | 1.3 | 2.6 | 5.21 | 10.42 | 15.63 | 20.83 | 26.04 | 31.25 | 36.46 | 41.67 | ||||||
Catetan:AbdiFitur panyalindungan reureuh lila kontroler cerdas standar pabrik nyaéta I²T panyalindungan waktos tibalik universal: I2TL=(1.5Ir) 2t, tL-reureuh lila 1.5Ir waktos setélan, TL- Waktos aksi reureuh lila, Kasalahan waktos operasi ±15%.
Diagram kabel sirkuit sekundér tipe-R RDW8HU-2500/4000/6300 Fungsi terminal sareng interpretasi simbol
| Nomer terminal | Pedaran Fungsi | Simbol | Parafrase | Catetan |
| 1, 2 | Input daya bantu: AC230V, AC400V, DC220V, DC110V | RDW8HU | Pemutus sirkuit universal RDW8HU | |
| 3, 4, 5 | Kontak bantu trip gangguan, kapasitas kontak: AC250V, 3A | S1~S4 | Lampu sinyal | Pangguna disayogikeun |
| 20 | Tanah (PE) | TA | Transformator arus | |
| 21, 22, 23, 24 | Pangukuran sinyal tegangan, 21 disambungkeun ka fase N, 22 disambungkeun ka fase A, 23 disambungkeun ka fase B, 24 disambungkeun ka fase C | SAL | saklar mikro | |
| 27, 28 | Pelepasan tegangan handap | SB1 | Tombol muka | Pangguna disayogikeun |
| 29, 30 | Pelepasan shunt | SB2 | Tombol nutup | Pangguna disayogikeun |
| 31, 32 | Panutup éléktromagnét | X | Panutup éléktromagnét | |
| 33,34,35 | Mékanisme operasi listrik (panyimpen énergi listrik), 37 disambungkeun ku jalur héjo, 38 disambungkeun ku jalur hideung, 39 disambungkeun ku jalur beureum | F | Pelepasan shunt | |
| 36~48 | Terminal kontak bantu | Q | Pelepasan tegangan handap | |
| ★Kusabab tegangan sirkuit utama séri ieu nyaéta tegangan luhur, pangukuran sinyal tegangan tina kontroler tipe R/H 21,22/23,24 kedah disambungkeun kana modul konvérsi tegangan. | M | Mékanisme operasi listrik | ||
| SA | Saklar perjalanan mékanisme operasi listrik | |||
| Fu | sekering | Pangguna disayogikeun | ||
| PE | Kawat taneuh | |||
| N | Nétral (fase N) | |||
| A, B, C | Garis fase | |||
| AX | Kontak bantu | |||
Diagram kabel sirkuit sekundér tipe-H RDW8HU-2500/4000/6300 Fungsi terminal sareng interpretasi simbol
| Nomer terminal | Pedaran Fungsi | Simbol | Parafrase | Catetan |
| 1, 2 | Input daya bantu: AC230V, AC400V, DC220V, DC110V | RDW8HU | Pemutus sirkuit universal RDW8HU | |
| 3, 4, 5 | Kontak bantu trip gangguan, kapasitas kontak: AC250V, 3A | S1~S4 | Lampu sinyal | Pangguna disayogikeun |
| 10, 11 | Kaluaran antarmuka komunikasi, 10 nyaéta (+), 11 nyaéta (-) (Catetan: Modeu komunikasi Modbus-RTU standar) | TA | Transformator arus | |
| 12~15 | DO1, kaluaran sinyal anu tiasa diprogram, kapasitas kontak: AC250V, 3A | SAL | Saklar Mikro | |
| 14, 15 | DO2DO3, kaluaran sinyal muka, kapasitas kontak: AC250V, 3A | SB1 | Tombol muka | Pangguna disayogikeun |
| 16, 17 | DO4, kaluaran sinyal panutupan, kapasitas kontak: AC250V, 3A | SB2 | Tombol nutup | Pangguna disayogikeun |
| 18, 19 | Tanah (PE) | X | Panutup éléktromagnét | |
| 20 | Pangukuran sinyal tegangan, 21 disambungkeun ka fase N, 22 disambungkeun ka fase A, 23 disambungkeun ka fase B, 24 disambungkeun ka fase C | F | Pelepasan shunt | |
| 21, 22, 23, 24 | Input transformator N éksternal | Q | Pelepasan tegangan handap | |
| 25, 26 | Pelepasan tegangan handap | M | Mékanisme operasi listrik | |
| 27, 28 | Pelepasan shunt | SA | Saklar perjalanan mékanisme operasi listrik | |
| 29, 30 | Panutup éléktromagnét | Fu | sekering | Pangguna disayogikeun |
| 31, 32 | Mékanisme operasi listrik (panyimpen énergi listrik), 37 disambungkeun ku jalur héjo, 38 disambungkeun ku jalur hideung, 39 disambungkeun ku jalur beureum | PE | Kawat taneuh | |
| 33,34,35 | Terminal kontak bantu | N | Nétral (fase N) | |
| 36~48 | A, B, C | Garis fase | ||
| ★Kusabab tegangan sirkuit utama séri ieu nyaéta tegangan luhur, pangukuran sinyal tegangan tina kontroler tipe R/H 21,22/23,24 kedah disambungkeun kana modul konvérsi tegangan. | AX | Kontak bantu | Rakitan selektif | |
| Modul ST-DP | Parameter ieu diperyogikeun nalika mode komunikasi nyaéta Profibus-DP | Rakitan selektif | ||
| Modul Daya ST | Fungsi komunikasi nalika diperyogikeun | Rakitan selektif | ||
| Modul Relay ST201 | Fungsi komunikasi nalika diperyogikeun | |||
Pemutus Sirkuit Universal Calakan RDW8HU-2500 (Jenis laci)
| Arus anu dipeunteun (A) | Ketebalan busbar H(mm) |
| 630,800,1000,1250,1600 | 15 |
| 2000, 2500 | 20 |
RDW8HU-2500 Arusna pakait jeung ketebalan busbar
Pemutus Sirkuit Universal Cerdas RRDW8HU-2500 (diperbaiki)
| Arus anu dipeunteun (A) | Ketebalan busbar H(mm) |
| 630,800,1000,1250,1600 | 15 |
| 2000, 2500 | 20 |
RDW8HU-2500 Arus pakait sareng ketebalan busbar
Pemutus Sirkuit Universal Calakan RDW8HU-4000 (Tipe Laci)
| Arus anu dipeunteun (A) | Ketebalan busbar H(mm) |
| 800, 1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000 | 20 |
Arusna pakait jeung ketebalan busbar
Pemutus Sirkuit Universal Calakan RDW8HU-4000 (diperbaiki)
| Arus anu dipeunteun (A) | Ketebalan busbar H(mm) |
| 800, 1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000 | 20 |
Arusna pakait jeung ketebalan busbar
Pemutus Sirkuit Universal Calakan RDW8HU-6300 (diperbaiki)
| Arus anu dipeunteun (A) | Ketebalan busbar H(mm) |
| 4000 | 25 |
| 5000~6300 | 30 |
Pemutus Sirkuit Universal Calakan RDW8HU-6300 (Jenis laci)
Pemutus Sirkuit Universal Calakan RDW8HU-6300 (Jenis laci)